102 Rockwell Automation Publication 1756-UM001M-EN-P - February 2012
Chapter 5 Communication Networks
Communicate Over a DH+ Network
For the controller to communicate to a workstation or other device over a DH+
network, use RSLinx Classic software to do the following:
Specify a unique link ID for each ControlLogix backplane and additional
network in the communication path.
Configure the routing table for the 1756-DHRIO module.
The 1756-DHRIO module can route a message through up to four
communication networks and three chassis. This limit applies only to the routing
of a message and not to the total number of networks or chassis in a system.
For more information about configuring and using a DH+ network via the 1756-
DHRIO module, see the Data Highway Plus-Remote I/O Communication
Interface Module User Manual, publication 1756-UM514
.
Universal Remote I/O (RIO)
Communication
For universal remote I/O communication, you have two module options for use
in the ControlLogix chassis. This table lists the RIO modules and capabilities.
When a channel on the 1756-DHRIO module is configured for remote I/O, the
module acts as a scanner for a universal remote I/O network. The controller
communicates to the module to send and receive the I/O data on the universal
remote I/O network.
The 1756-RIO module can act as a scanner or adapter on a remote I/O network.
In addition to digital and block-transfer data, the 1756-RIO module transfers
analog and specialty data without message instructions.
Table 26 - RIO Modules and Capabilities
RIO Module Is used to
1756-RIO Function as an RIO scanner and adapter.
Support connections to 32 racks in any combination of rack size or block transfers.
Update data to the ControlLogix controller by using scheduled connections.
1756-DHRIO Function as an RIO scanner.
Support either 32 logical rack connections or 16 block-transfer connections per channel.
Establish connections between controllers and I/O adapters.
Distribute control so that each controller has its own I/O.