Rockwell Automation Publication 1756-UM001M-EN-P - February 2012 145
I/O Modules Chapter 8
Other Devices that Can be Added While Online
1305-BAXXA drives
1336E-IMPACT™Drive-EN1 drive
1336F-PLUS™IIDrive-EN1drive
1336R-REGENBrake-EN1 brake
1336S-PLUSDriveLG-EN1 drive
1336S-PLUSDriveSM-EN1 drive
1336T-FORCE™DriveCNA-EN1 drive
1336T-FORCEDrivePLC-EN1 drive
1336T-FORCEDriveStd-EN1 drive
1397DigitalDCDrive-EN1 drive
150 SMC™ FLEX motor controller
150-SMC™DialogPlus-EN1 motor controller
1757-FFLDC ControlNet Foundation Fieldbus device
2364F RGU-EN1 bus supply
48MS-SN1PF1-M2 Multivision Sensor
5XRF RFID interface device
Online Additions - ControlNet Considerations
ControlNet considerations that must be made depend upon the ControlLogix
ControlNet modules you are using.
1756-CNB and 1756-CNBR Modules
When you add I/O to the ControlNet network via the 1756-CNB or
1756-CNBR modules while online, these considerations must be made:
Digital I/O modules can be added as rack-optimized connections if the
parent module is already configured with rack-optimized connections.
Digital I/O modules can also be added as direct connections.
Analog I/O modules can be added only as direct connections.
Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.
TIP
While you can add a new digital I/O module to an existing rack-optimized
connection, you cannot add rack-optimized connections while online.