EasyManua.ls Logo

Allen-Bradley 1756-L72

Allen-Bradley 1756-L72
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
146 Rockwell Automation Publication 1756-UM001M-EN-P - February 2012
Chapter 8 I/O Modules
If you plan to add large amounts of I/O to the ControlNet network,
dedicate one ControlNet network for I/O. For the dedicated ControlNet
network, verify that there is little or none of the following:
HMI traffic
MSG traffic
Programming workstations
Requested Packet Intervals (RPIs) faster than 25 ms for unscheduled
modules can overload the 1756-CNB or 1756-CNBR communication
module. To avoid the overload, make these considerations:
Use a NUT of 10 ms or more.
Keep the SMAX and UMAX values as small as possible.
If the module has a Real Time Sample (RTS), it should be disabled or set
to a rate that is greater than the RPI.
You can add I/O modules until you reach these limits:
75% of CPU utilization of the 1756-CNB or 1756-CNBR
communication module.
Plan for a CPU-use increase of 1...4% of the 1756-CNB or 1756-
CNBR module for each I/O module you add, depending on the RPI.
48 connections on the 1756-CNB or 1756-CNBR communication
module.
Less than 400,000 unscheduled bytes per second are displayed in
RSNetWorx for ControlNet software after the network has been
scheduled.
1756-CN2, 1756-CN2R, 1756-CN2RXT Modules
The use of 1756-CN2/B, 1756-CN2R/B, and 1756-CN2RXT modules
provides increased capacity for adding I/O while online compared to 1756-CNB
or 1756-CNBR modules. With this increased capacity, you can easily add I/O
and increase ControlNet connections used with significantly less impact on the
overall system.

Table of Contents

Other manuals for Allen-Bradley 1756-L72

Related product manuals