194 Rockwell Automation Publication 1756-UM001M-EN-P - February 2012
Chapter 13 SIL 2 Certification
Typical SIL2 Configurations
SIL2-certified ControlLogix systems can be used in non-redundancy or
redundancy configurations. For the purposes of documentation, the various levels
of availability that can be achieved by using various ControlLogix system
configurations are referred to as fail-safe, high-availability, or fault-tolerant.
This table lists each system configuration and the hardware that is part of the
systems safety loop.
Table 52 - SIL2 Configurations and Hardware Summary
With this system configuration The safety loop includes
Fail-safe Configuration, page 195 Nonredundant controller
Nonredundant communication modules
Nonredundant remote I/O
High-availability Configuration, page 196 Redundant controllers
Redundant communication modules
Nonredundant remote I/O
Fault-tolerant Configuration
, page 197 Redundant controllers
Redundant communication modules
Redundant remote I/O
I/O termination boards
IMPORTANT
Note that the system user is responsible the tasks listed here when any of
the ControlLogix SIL2 system configurations are used:
The setup, SIL rating, and validation of any sensors or actuators connected to the
ControlLogix control system.
Project management and functional testing.
Programming the application software and the module configuration according
to the descriptions in the following chapters.
The SIL2 portion of the certified system excludes the development tools
and display/human machine interface (HMI) devices; these tools and
devices are not part of the safety loop.