24 SSI Servo Module
Publication
1756-IN595A-EN-P - March 2004
ESD Immunity IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 80MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5:
+
2kV line-earth (CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Enclosure Type Rating None (open-style)
Certifications
(when product is marked)
UL UL Listed Industrial Control Equipment
CSA CSA Certified Process Control Equipment
CSA CSA Certified Process Control Equipment for
Class I, Division 2 Group A,B,C,D Hazardous
Locations
CE
(3)
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
(3)
Australian Radiocommunications Act,
compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
Maximum wire size requires the extended-depth RTB housing (1756-TBE).
(2)
Use the conductor category information for planning conductor routing as described in the system
level installation manual. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
number 1770-4.1.
(3)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.