EasyManua.ls Logo

Allen-Bradley 1794-IE8H - 1794-OE8 H Calibration Item Byte Channel-Mask

Allen-Bradley 1794-IE8H
146 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Publication 1794-UM063A-EN-P - March 2006
Calibrate Your Module 5-17
1794-OE8H Calibration Item Byte Channel-Mask
The Calibration item byte channel-mask uses each bit of the byte to
correspond to one channel: where 1 is calibrate this channel and 0 is do not
calibrate this channel. The LSB corresponds to channel 0, e.g., 0x03 >
channel
0 and 1 have to be calibrated. Only one channel can be calibrated at a time. If
there are more channels selected within the calibration commands, the I/O
module signals an error.
Table 5.14 1794-OE8H Calibration Item Byte Value Identifier List
Identifier (Decimal) Value Access Rule
0 Offset channel 0 Read/write
……
7 Offset channel 7
8 Gain channel 0
……
15 Gain channel 7
16 Offset current-read-back channel 0
……
23 Offset current-read-back channel 7
24 Gain current-read-back channel 0
……
31 Gain current-read-back channel 7
32 Offset voltage-read-back channel 0
……
39 Offset voltage-read-back channel 7
40 Gain voltage-read-back channel 0 Read/write
……
47 Gain voltage-read-back channel 7
48 Status mask calibration
49 Reserved
50 Calibration day
51 Calibration month
52 Calibration year
53 Checksum over calibration values Read
54…255 Reserved
76543210
Calibrate Channel 0
:
Calibrate Channel 1
Calibrate Channel 7

Table of Contents