Publication 1794-UM063A-EN-P - March 2006
Input, Output and Configuration Files for the Analog I/O Modules on the ControlNet Network 4-7
Device Actions
Device actions include:
Communication fault behavior
Idle state behavior
Input data behavior upon module removal
Communication Fault Behavior
You can configure the response to a communication fault for
each I/O module in its system. Upon detection of a communication fault,
the module can:
Leave the module output data in its last state (hold last state)
Reset the module output data to zero (reset)
Apply fault state data to the module output
Idle State Behavior
The FLEX I/O HART module can detect the state of the controlling
processor or scanner. Only 2 states can be detected: Run mode, or Program
mode (idle).
When Run mode is detected, the adapter copies the output data received from
the processor to the corresponding module output. When Program mode is
detected, the I/O module can be configured to:
Leave the module output data in its last state (hold last state)
Reset the module output data to zero (reset)
Apply fault state data to the module output

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 1794-IE8H and is the answer not in the manual?

Allen-Bradley 1794-IE8H Specifications

General IconGeneral
BrandAllen-Bradley
Model1794-IE8H
CategoryControl Unit
LanguageEnglish

Related product manuals