EasyManua.ls Logo

Allen-Bradley Compact 5000 - Fault and Status Reporting

Allen-Bradley Compact 5000
110 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 5069-UM003A-EN-P - May 2018 25
Compact 5000 I/O Serial Module Features Chapter 3
RPI Range
Fault and Status Reporting
The Compact 5000 I/O serial modules report fault and status data along with
channel data. Fault and status data is reported in the following ways:
Logix Designer application
•Module Status indicators
For more information on fault reporting, see the full chapter, Troubleshoot
Yo ur Mo dul e o n p a g e 7 1 .
Protocol Setting Range of RPI
Generic ASCII 2 ms…750 ms (by 0.1 ms)
Modbus Master 6 ms…750 ms (by 0.1 ms)
Modbus Slave 6 ms…750 ms (by 0.1 ms)
IMPORTANT If the RPI is not a multiple of 0.1 ms, round the number down to the
closest multiple value of 0.1 ms. For example, if the RPI is 2.37 ms, round
to 2.3 ms.
Depending on the software version, you can set each channel value
separately.

Table of Contents

Related product manuals