50 Rockwell Automation Publication 5069-UM003A-EN-P - May 2018
Chapter 4 Configure Compact 5000 I/O Serial Module
4. At the New Module window, configure the module properties and click
OK.
5. At the warning dialog box, make sure that Inhibit module connection is
selected and click Yes.
6. Close the Select Module Type dialog box.
To add additional remote I/O modules with this method, complete one of
the following:
If you cleared the Close on Create checkbox when you created the first
I/O module, repeat steps 3
6.
If you did not clear the Close on Create checkbox when you created the
first I/O module, repeat steps 2
6.