Rockwell Automation Publication 193-QR004B-EN-P - January 2017 19
Chapter 2
Configuration and Communication with a Logix™ Controller
You can manually add a preconfigured E300 relay offline to any Logix processor, or you can manually add a
preconfigured E300 relay online to a ControlLogix™ processor. You can perform an upload command to retain all of the
E300 relay’s configuration settings.
Before You Begin
To complete this chapter, you must have completed the requirements in Appendix 1.
What You Need
An E300 relay that is set up and connected to a communication network
Follow These Steps
In this chapter, you will perform the following steps to set up communication between a Logix controller and the
E300 relay.
1. Add the E300 relay device profile to the project
2. Upload the configuration settings of the preprogrammed E300 relay to the project
3. Set the E300 relay operation mode
4. Set the full-load current (FLA)
5. Download the project to the Logix controller
6. Use an Output tag to control the motor
Add an E300 Overload Relay to a Studio 5000™ or RSLogix 5000 Project
Follow these steps to manually add an E300 relay and retain its configuration settings with a new or existing RSLogix
5000 or Studio 5000 project.