Rockwell Automation Publication 193-QR004B-EN-P - January 2017 29
Chapter 3
Device Configuration Using the Diagnostic Station
The E300 Electronic Overload Relay supports a Diagnostic Station on the E300 Expansion Bus (requires Control
Module firmware v3.000 and higher). The Diagnostic Station allows you to view any E300 relay parameter and edit any
configuration parameter. This chapter explains how to use the navigation keys on the Diagnostic Station to view a
parameter and edit the minimum required configuration parameters.
Before You Begin
Before you use the diagnostic station, you must first have completed the installation explained in Chapter 1.
What You Need
E300 relay with diagnostic station that is connected to an E300 expansion bus
Follow These Steps
The E300 Diagnostic Station allows you to edit configuration parameters by using a group menu system or by a linear
list. At a minimum you must configure ConfigPreset (Parameter 164) and FLASetting (Parameter 171) to make the
E300 function properly. To start the navigation menu, press the key. You are prompted to view parameters by
groups or parameters in a linear list.
Edit Configuration Preset (Parameter 164)
1. Choose a navigation method and display ConfigPreset (Parameter 164)
2. Press the key to modify the value.