PowerFlex 400 Adjustable Frequency AC Drive Quick Start English-13
Before Applying Power to the Drive
1. Confirm that all inputs are connected to the correct terminals and are
secure.
2. Verify that AC line power at the disconnect device is within the rated
value of the drive.
3. Verify that any digital control power is 24 volts.
4. Verify that the Sink (SNK)/Source (SRC) Setup DIP Switch is set to
match your control wiring scheme.
Important: The default control scheme is Source (SRC). The Stop
terminal is jumpered (I/O Terminals 01 and 11) to allow
starting from the keypad. If the control scheme is changed
to Sink (SNK), the jumper must be removed from I/O
Terminals 01 and 11 and installed between I/O Terminals
01 and 04.
5. Verify that the Stop input is present or the drive will not start.
Important: If I/O Terminal 01 is used as a stop input, the jumper
between I/O Terminals 01 and 11 must be removed.
6. Verify that the Analog I/O DIP Switches are set to 10 volts.
Applying Power to the Drive
7. Apply AC power and control voltages to the drive.
8. Familiarize yourself with the integral keypad features before setting
any Program Group parameters.
Start, Stop, Direction and Speed Control
Factory default parameter values allow the drive to be controlled from
the integral keypad. No programming is required to start, stop, and
control speed directly from the integral keypad.
If a fault appears on power up, refer to page 25 for an explanation of the
fault code. For complete troubleshooting information, refer to the
PowerFlex 400 User Manual supplied with the drive.
Prepare For Drive Start-Up
!
ATTENTION: Power must be applied to the drive to perform the
following start-up procedures. Some of the voltages present are at
incoming line potential. To avoid electric shock hazard or damage to
equipment, only qualified service personnel should perform the
following procedure. Thoroughly read and understand the procedure
before beginning. If an event does not occur while performing this
procedure, Do Not Proceed. Remove All Power including user
supplied control voltages. User supplied voltages may exist even when
main AC power is not applied to the drive. Correct the malfunction
before continuing.
WWW.KORATGROUP.COM

Other manuals for Allen-Bradley PowerFlex 400

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 400 and is the answer not in the manual?

Allen-Bradley PowerFlex 400 Specifications

General IconGeneral
Input Voltage200-240VAC, 380-480VAC, 500-600VAC
Output Voltage0-Input Voltage
Output Frequency0-400 Hz
CommunicationEtherNet/IP
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short Circuit
Operating Temperature-10°C to 50°C (14°F to 122°F)
Storage Temperature-40°C to 70°C (-40°F to 158°F)
Humidity5-95% non-condensing
Enclosure RatingIP20
Horsepower0.5-20 HP
Control MethodV/Hz, Sensorless Vector Control