Programming and Parameters 3-29
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group (continued)
A453 [Boost Select] Related Parameter(s): d004, P101, P102
Sets the boost voltage (% of P101 [Motor NP Volts]) and redefines the Volts per Hz curve.
(1)
(1)
Drive may add additional voltage unless option 5 is selected.
Options 1
30.0, VT”
Variable Torque
2
35.0, VT”
3
40.0, VT”
4
45.0, VT”
5 “0
.0 no IR
Constant Torque
6 “0
.0”
7 “2
.5, CT”
[Default for
3.7, 5.5, 7.5 & 11.0 kW
(5.0, 7.5, 10.0 & 15.0 HP) Drives]
8 “5
.0, CT” (Default)
9 “7
.5, CT”
10
10.0, CT”
11
12.5, CT”
12
15.0, CT”
13
17.5, CT”
14
20.0, CT”
% P102 [Motor NP Hertz]
% P101 [Motor NP Volts]
100
50
1/2 [Motor NP Volts]
1/2
[Motor NP Hertz]
4
3
2
1