EasyManua.ls Logo

Allen-Bradley PowerFlex 4M - Page 69

Allen-Bradley PowerFlex 4M
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programming and Parameters 3-29
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group (continued)
A453 [Boost Select] Related Parameter(s): d004, P101, P102
Sets the boost voltage (% of P101 [Motor NP Volts]) and redefines the Volts per Hz curve.
(1)
(1)
Drive may add additional voltage unless option 5 is selected.
Options 1
30.0, VT”
Variable Torque
2
35.0, VT”
3
40.0, VT”
4
45.0, VT”
5 “0
.0 no IR
Constant Torque
6 “0
.0”
7 “2
.5, CT”
[Default for
3.7, 5.5, 7.5 & 11.0 kW
(5.0, 7.5, 10.0 & 15.0 HP) Drives]
8 “5
.0, CT” (Default)
9 “7
.5, CT”
10
10.0, CT”
11
12.5, CT”
12
15.0, CT”
13
17.5, CT”
14
20.0, CT”
% P102 [Motor NP Hertz]
% P101 [Motor NP Volts]
100
50
1/2 [Motor NP Volts]
1/2
[Motor NP Hertz]
4
3
2
1
0 50 100
Settings
5-14

Table of Contents

Related product manuals