EasyManuals Logo
Home>Allen-Bradley>Controller>PowerFlex 4M

Allen-Bradley PowerFlex 4M User Manual

Allen-Bradley PowerFlex 4M
118 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #70 background imageLoading...
Page #70 background image
3-30 Programming and Parameters
PowerFlex 4M Adjustable Frequency Drive FRN 1.xx - 2.xx User Manual
Publication 22F-UM001D-EN-E
Advanced Program Group (continued)
A457 [Maximum Voltage]
Sets the highest voltage the drive will output.
Values Default Drive Rated Volts
Min/Max: 20/Drive Rated Volts
Display: 1 VAC
A458 [Program Lock]
Protects parameters against change by unauthorized personnel.
Options 0 “U
nlocked” (Default)
1 “L
ocked”
A459 [Testpoint Sel]
Used by Rockwell Automation field service personnel.
Values Default 400
Min/Max: 0/FFFF
Display: 1 Hex
A461 [Motor NP FLA]
Set to the motor nameplate rated full load amps.
Values Default Drive Rated Amps
Min/Max: 0.1/(Drive Rated Amps × 2)
Display: 0.1 Amps