EasyManua.ls Logo

Allen-Bradley PowerFlex 70

Allen-Bradley PowerFlex 70
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48 Rockwell Automation Publication 20A-UM001N-EN-P - July 2013
Chapter 1 Programming and Parameters
Restart Modes
179 [Sleep Wake Ref]
Selects the source of the input controlling the
Sleep-Wake function.
Default:
Options:
2
1
2
“Analog In 2
“Analog In 1
“Analog In 2
178
180
183
320
327
180 [Wake Level]
Defines the analog input level that starts the
drive.
Default:
Min/Max:
Units:
6.000 mA, 6.000 Volts
[Sleep Level]/20.000 mA [Sleep
Level]/10.000 Volts
0.001 mA
0.001 Volts
178
179
181
183
181 [Wake Time]
Defines the amount of time at or above [Wake
Level] before a Start is issued.
Default:
Min/Max:
Units:
1.0 Secs
0.0/1000.0 Secs
0.1 Secs
178
180
182 [Sleep Level]
Defines the analog input level that stops the
drive.
Default:
Min/Max:
Units:
5.000 mA, 5.000 Volts
4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
0.001 mA
0.001 Volts
178
180
183
183 [Sleep Time]
Defines the amount of time at or below [Sleep
Level] before a Stop is issued.
Default:
Min/Max:
Units:
1.0 Secs
0.0/1000.0 Secs
0.1 Secs
182
DYNAMIC CONTROL (file D)
Power Loss
177 [Gnd Warn Level]
Sets the level where a ground warning fault
occurs. Configure with [Alarm Config 1].
Default:
Min/Max:
Units:
3.0 Amps
1.0/5.0 Amps
0.1 Amps
259
184 [Power Loss Mode]
Sets the reaction to a loss of input power. Power
loss is recognized when:
DC bus voltage is 73% of [DC Bus Memory]
and [Power Loss Mode] is set to “Coast”.
DC bus voltage is 82% of [DC Bus Memory]
and [Power Loss Mode] is set to “Decel”.
Default:
Options:
0
0
1
2
3
4
5
“Coast”
“Coast”
“Decel”
“Continue”
“Reserved”
“Reserved”
“Decel 2 Stop”
013
185
361
366
“Coast” = Disable drive and enable the motor to coast.
“Decel” = Decelerate the motor at a rate that regulates the DC Bus until the loads Kinetic
Energy can no longer power the drive.
“Continue” = Enable the drive to power the motor down to 50% of the nominal DC Bus
voltage.
Refer to the PowerFlex 70EC/700VC Reference Manual, publication PFLEX-RM004
, for
additional information.
185 [Power Loss Time]
Sets the time that the drive remains in power
loss mode before a fault is issued.
Default:
Min/Max:
Units:
0.5 Secs
0.0/60.0 Secs
0.1 Secs
184
187 [Load Loss Level]
Sets the percentage of motor nameplate torque
where a load loss alarm occurs.
Default:
Min/Max:
Units:
200.0%
0.0/800.0%
0.1%
211
259
188 [Load Loss Time]
Sets the time that current is below the level set
in [Load Loss Level] before a fault occurs.
Default:
Min/Max:
Units:
0.0 Secs
0.0/300.0 Secs
0.1 Secs
187
File D
Group
No.
Parameter Name and Description
See page 14 for symbol descriptions
Values
Related
E C v2
E C v2
E C v2
E C v2
E C v2
E C v2
E C
E C v4
ATTENTION: To guard against drive damage, a minimum line
impedance must be provided to limit inrush current when the
power line recovers. Provide an input impedance equal or
greater than the equivalent of a 5% transformer with a VA rating
6 times the drives input VA rating.
E C v2
E C v2

Other manuals for Allen-Bradley PowerFlex 70

Related product manuals