Component Test Procedures 2-9
1. Remove power from the drive. Refer to Removing Power from the
Drive on page 3-3.
2. Remove the covers from the power structure. Refer to Removing the
Covers from the Power Structure on page 3-13.
3. Disconnect the Main Fan Inverters power supply cables in order to
prevent them from running during these tests.
4. Disconnect the fiber optic cables that connect the ASIC board to the
three Gate Driver boards at the Gate Driver board ends.
5. Disconnect the plug from the X6 connector on the ASIC board.
6. Make the following connections from a High Voltage DC Test Power
Supply to X6 on the ASIC board using a new connector plug.
7. Disconnect the DC+ wire from each of the three Gate Driver boards.
8. Connect the High Voltage DC Test Power Supply DC- to the DC- Bus
Bar.
!
ATTENTION: Running the drive without the Main Fan
Inverters could cause the drive to overheat or fault. Possible
equipment damage could occur. You must replace the fuses
before running the drive.
From High Voltage DC Test
Power Supply
To this pin on the X6 on ASIC
Board
DC+ 1
DC- 3
Jumper pin 1 to pin 2 on connector
HL
DC+ DC-