EasyManuals Logo

Allen-Bradley PowerFlex 750 Series Programming Manual

Allen-Bradley PowerFlex 750 Series
548 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
106 Rockwell Automation Publication 750-PM001N-EN-P - February 2017
Chapter 3 Drive Port 0 Parameters
PROTECTION
Predictive Maintenance
502 MtrBrngTotalLife
Motor Bearing Total Life
Total number of hours expected over the life of the motor bearings.
Units:
Default:
Min/Max:
Hrs
0.00
0.00 / 21474836.47 (31 bits)
RW 32-bit
Integer
503 MtrBrngElpsdLife
Motor Bearing Elapsed Life
Accumulated hours of motor bearing run time. Hours are accumulated any time the
drive is running greater than zero speed.
Use P472 [PredMaint Reset] to reset this parameter.
Units:
Default:
Min/Max:
Hrs
0.00
0.00 / 21474836.47 (31 bits)
RO 32-bit
Integer
504 MtrBrngRemainLif
Motor Bearing Remaining Life
Remaining number of hours until estimated end of life for motor bearings, and is the
difference between P502 [MtrBrngTotalLife] and P503 [MtrBrngElpsdLife].
Use P472 [PredMaint Reset] to reset this parameter.
Units:
Default:
Min/Max:
Hrs
0.00
–21474836.48 / 21474836.47
RO 32-bit
Integer
505 MtrBrngEventLvl
Motor Bearing Event Level
Percent of total expected motor bearing life for which an early warning alarm or fault
can be programmed.
Units:
Default:
Min/Max:
%
80.000
0.000 / 100.000
RW Real
506 MtrBrngEventActn
Motor Bearing Event Action
Configures the response to a motor bearing event, which occurs when P505
[MtrBrngEventLvl] is met or exceeded.
“Ignore” (0) – No action is taken.
Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.
Default:
Options:
0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop
5 = “Flt CL Stop
RW 32-bit
Integer
507 MtrBrng ResetLog
Motor Bearing Reset Log
Total number of resets performed on the P503 [MtrBrngElpsdLife] parameter.
Default:
Min/Max:
0
0 / 255 (unsigned 8 bits)
RO 32-bit
Integer
508 MtrLubeElpsdHrs
Motor Lubricant Elapsed Hours
Accumulated hours since the most recent lubrication of the motor bearings. Can be reset
without restriction.
Use P472 [PredMaint Reset] to reset this parameter.
Units:
Default:
Min/Max:
Hrs
0.00
0.00 / 21474836.47
RO 32-bit
Integer
509 MtrLubeEventLvl
Motor Lubricant Event Level
Number of hours between scheduled lubrications of the motor bearings. Used for an
early warning alarm or fault according to P510 [MtrLubeEventActn]. Event is disabled
when set to 0.
Units:
Default:
Min/Max:
Hrs
0.000
0.000 / 2147483648.000
RW Real
510 MtrLubeEventActn
Motor Lubricant Event Action
Configures the response to a motor bearing lubrication event, which occurs when P509
[MtrLubeEventLvl] is met or exceeded.
“Ignore” (0) – No action is taken.
Alarm” (1) – Type 1 alarm indicated.
“Flt Minor” (2) – Minor fault indicated. If running, drive continues to run.
Enable with P950 [Minor Flt Cfg]. If not enabled, acts like a major fault.
“FltCoastStop” (3) – Major fault indicated. Coast to Stop.
“Flt RampStop” (4) – Major fault indicated. Ramp to Stop.
“Flt CL Stop” (5) – Major fault indicated. Current Limit Stop.
Default:
Options:
0 = “Ignore”
0 = “Ignore”
1 = “Alarm”
2 = “Flt Minor”
3 = “FltCoastStop”
4 = “Flt RampStop
5 = “Flt CL Stop
RW 32-bit
Integer
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type

Table of Contents

Other manuals for Allen-Bradley PowerFlex 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 750 Series and is the answer not in the manual?

Allen-Bradley PowerFlex 750 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 750 Series
CategoryController
LanguageEnglish

Related product manuals