Rockwell Automation Publication 750-PM001N-EN-P - February 2017 109
Drive Port 0 Parameters Chapter 3
SPEED CONTROL
Speed Limits
526
527
528
Skip Speed 1
Skip Speed 2
Skip Speed 3
Skip Speed n
Sets a frequency at which the drive will not operate. Parameters are disabled if set to 0.
Units:
Default:
Min/Max:
Hz
RPM
0.00
P521 [Max Rev Speed] / P520 [Max Fwd
Speed]
RW Real
529 Skip Speed Band
Skip Speed Band
Sets the bandwidth around a skip speed. [Skip Speed Band] is split, applying 1/2 above
and 1/2 below the skip speed. The same bandwidth applies to all skip speeds. Parameter
is disabled if set to 0.
Units:
Default:
Min/Max:
Hz
RPM
0.00
0.00 / Based on P27 [Motor NP Hertz]/P28
[Motor NP RPM] and Voltage Class
RW Real
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
File
Group
No. Name
Description
Values
Read-Write
Data Type
SPEED CONTROL
Speed Ramp Rates
535
536
Accel Time 1
Accel Time 2
Acceleration Time n
Sets the acceleration rate for all speed changes. Defined as the time to accelerate from 0
to P27 [Motor NP Hertz] or P28 [Motor NP RPM], according to the setting in P300 [Speed
Units]. Selection between Acceleration Time 1 and Acceleration Time 2 is controlled by a
digital input function (see Digin Functions) or by Logic Command (sent over a
communication network or DeviceLogix).
Units:
Default:
Min/Max:
Secs
10.00
0.00 / 3600.00
RW Real
537
538
Decel Time 1
Decel Time 2
Deceleration Time n
Sets the deceleration rate for all speed changes. Defined as the time to decelerate from
P27 [Motor NP Hertz] or P28 [Motor NP RPM] to 0, according to the setting in P300
[Speed Units]. Selection between Deceleration Time 1 and Deceleration Time 2 is
controlled by a digital input function (see Digin Functions) or by Logic Command (sent
over a communication network or DeviceLogix). Some stop modes (see P370 and P371)
will cause the programmed decel time to be ignored during a stop command.
Units:
Default:
Min/Max:
Secs
10.00
0.00 / 3600.00
RW Real
539 Jog Acc Dec Time
Jog Acceleration Deceleration Time
Acceleration and deceleration rates while commanding jog (uses a jog speed reference).
Units:
Default:
Min/Max:
Secs
10.00
0.00 / 3600.00
RW Real
540 S Curve Accel
S Curve Acceleration
Sets the percentage of accel time applied to the ramp to soften (reduce jerk) the
acceleration. Time is added, 1/2 at the beginning and 1/2 at the end of the ramp.
Units:
Default:
Min/Max:
%
0.000
0.000 / 100.000
RW Real
541 S Curve Decel
S Curve Deceleration
Sets the percentage of decel time applied to the ramp to soften (reduce jerk) the
deceleration. Time is added, 1/2 at the beginning and 1/2 at the end of the ramp.
Units:
Default:
Min/Max:
%
0.000
0.000 / 100.000
RW Real
0.0
10.0
20.0
30.0
40.0
50.0
60.0
70.0
0.0 1.0 2.0 3.0 4.0 5.0 6.0
Seconds
Hz

Table of Contents

Other manuals for Allen-Bradley PowerFlex 750 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 750 Series and is the answer not in the manual?

Allen-Bradley PowerFlex 750 Series Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 750 Series
CategoryController
LanguageEnglish

Related product manuals