Rockwell Automation Publication 750-PM001N-EN-P - February 2017 161
Drive Port 0 Parameters Chapter 3
File
Group
No. Display Name
Full Name
Description
Values
Read-Write
Data Type
DIAGNOSTICS
Fault/Alarm Info
950 Minor Flt Cfg
Minor Fault Configuration
RW 16-bit
Integer
Enables / Disables operation of the “Minor Fault” function, which allows the drive to continue running while some types of faults are present. In addition to setting
this parameter, the “Flt Minor” action must be selected for the condition that is desired to result in a minor fault (see P410 [Motor OL Actn] for an example).
951 Last Fault Code
Last Fault Code
The fault code of the first fault since the last reset. There is often a chain of faults that
occur during a breakdown. When troubleshooting, it is often helpful to know the first
fault. This parameter is for convenience. A comprehensive history of fault information is
available through the fault que (via HIM screens and / or software tools such as Drive
Explorer).
Default:
Min/Max:
0
0 / 424648720
RO 32-bit
Integer
952 Fault Status A
Fault Status A
RO 32-bit
Integer
Indicates the occurrence of conditions that have been configured as faults. These conditions are from 937 [Condition Sts 1].
See parameter 937 [Condition Sts 1] for bit descriptions.
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Enable
Default0000000000000000
Bit 1514131211109876543210
0 = Condition False
1 = Condition True
Options
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
ExtPrchrgErr
PosFdbkLoss
AuxFdbkLoss
AltFdbkLoss
PriFdbkLoss
Shear Pin 2
Shear Pin 1
Decel Inhib
OutPhaseLoss
InPhaseLoss
Load Loss
Motor OL
UnderVoltage
Power Loss
Default00000000000000000000000000000000
Bit 313029282726252423222120191817161514131211109876543210
0 = Condition False
1 = Condition True