Chapter 5 Detailed Function Introductions
114
Reference Freq.(Hz)
Frequency setting 2
Run command
UP command
DOWN command
STOP command
amplitude
Frequency setting1+Frequency setting 2 UP/DOWN Terminal Run
UP/DN reference
Figure. 5-3-3 UP/DOWN combination operation
NOTES: The terminal UP / DOWN is active only when P0.03 = 8 and when the inverter is in running state.
Operation Freq.(Hz)
UP/DOWN
reference Initial
Run Command
UP command
DOWN Command
Stop command
UP/DN reference amplitude
Figure. 5-3-4 UP/DOWN non-combination operation
13: FRE Free stopping
When defining terminal of the function is active, the inverter immediately locks PWM output, and exits
running state. Only during FRE releasing, the run command takes effect. Once the function is defined, no
matter the control mode (P0.07) is what, the function is active and is not subject to the limit of stop mode
(P1.10).
14: Forced stopping (based on deceleration time of abnormal stopping); 36: Forced stopping normally closed
Shut down slowly at deceleration time of abnormal stopping, it is subject to the limit of stop mode (P1.10).
15: Stopping process plus DC braking