Chapter 5 Detailed Function Introductions
2: dEc Decelerate 3: con constant
PE.06 Fault History 1 (Last One) Setting range: Table 5-14-1 [NULL]
PE.07 Fault History 2 Setting range: Table 5-14-1 [NULL]
PE.08 Fault History 3 Setting range: Table 5-14-1 [NULL]
Notes:
Memorize the types of the last 3 faults. See Table 5-14-1 for the details of faults.
PE.09 Total Operating time(h) Setting range: 0~65530h [0]
PE.10 Total Power On time(h) Setting range: 0~65530h [0]
PE.11 Total electric-consumption (MWh) Setting range: 0~9999MWh [0]
PE.12 Total electric-consumption (KWh) Setting range: 0~999KWh [0]
Notes:
Accumulated Operation Time (h): total time of the frequency inverter in the operation state
Accumulated Startup Time (h): accumulated time of the frequency inverter in the startup state
Accumulated Power Consumed (MWh): the highest level of accumulated power consumed by the frequency
Accumulated Power Consumed (KWh): the lowest level of accumulated power consumed by the frequency
inverter
5.16 Protection of parameters (Group PF)
PF.00 User password Setting range: 0~9999 [0]
Notes:
User password setting: The initial value of user password is 0, which means the password protection function
is invalid. At this state, user can access all parameters and parameters content of Group PF.
User Password Unlocking: after the user password is set and becomes effective, the password should be input
for unlocking to enter Group PF again. Otherwise, not all parameters in Group PF can be accessed.
Changing the user password: If password protection function is effective, right password must be input first to
unlock. After unlocking, select PF.00, re-change this parameter value, and press “ENTER” to save the value.
Now, the password changing is completed. Before changing the user password, remember to set PF.01 to 0, so
that all parameters are allowed to be changed.
The password will become effective when you press “PRG/ESC” to exit from Group PF if you set user
password.
Please remember the password, otherwise, you will have no access to all parameters of Group PF.
If you forget user password, please contact with manufacturer,
Example: Set the password to 1234, then exit from Group PF and unlock the user password. The process is
shown in Figure. 5-15-1 and Figure. 5-15-2.