Chapter 5 Detailed Function Introductions
If P6.00 is set to 0, function of stop at fixed length is disabled, but the calculated length is still effective.
The setting value must increase 200.0mm when P6.06 is modified by MODBUS communication. The corresponding
relation between communication value and actual used value (which can be displayed on the keypad) is as follows:
Reality used value (displayed on the keypad)) = Communication setting – 200.0mm
P6.07 Wobble frequency operation restart mode Setting range: 0.1 [0]
0: Start according to the state before
stoppingstopping
1: Re-start
Time(S)
Operation Freq.(Hz)
Central Freq.
Preset Freq.
Run command
Stop command
Fig. 5-6-3 Wobble frequency startup: Run in the state prior to stoppingstopping
Time(S)
Operation Freq.(Hz)
Central Freq.
Preset Freq.
Run command
Stop command
Fig. 5-6-4 Wobble frequency startup: Restart
P6.08 Save wobble frequency operating
parameters
Setting range: 0.1 [0]
0: not save 1: save
Notes:
Not save: The inverter does not save the wobble frequency operating parameters when power is off and
restart when power is on.
Save: The inverter will save the wobble-frequency operation parameters such as the operating frequency, and
operating direction (UP/DOWN) when power is off. The inverter will restart as the mode defined by P6.07
when power is on.
P6.09 Preset of wobble frequency
Setting range:
35R5GB and above: 0.00~400.0Hz [0.00 Hz]
3004GBand below: 0.00~650.0Hz [0.00 Hz]
P6.10 Holding time before wobble frequency Setting range: 0.0~3600s [0.0s]