Functi
on code
Parameter LCD display Setting range
Factory
setting
Mod.
MODB
US
address
P0.05
Frequency
setting
combination 1
Frequency
setting
combination 1
0: Frequency setting source 1
1: Frequency setting source 2
2: MIN (frequency setting
source 1, frequency setting
source 2)
3: MAX (frequency setting
source 1, frequency setting
source 2)
4: Frequency setting source 1 +
frequency setting source 2
5: Frequency setting source 1 -
frequency setting source 2
6: Frequency setting source
1×frequency setting source
2
7: Frequency setting source
1÷frequency setting source
2
8: |Frequency setting source
1-frequency setting source
2|
9: Frequency setting source 2 ×
(maximum output frequency
+ frequency setting source
1) ÷ maximum output
frequency
0 × 0105
P0.06
Frequency
setting
combination 2
Frequency
setting
combination 2
0~9, ditto.
It is enabled after defining FC
terminal and the terminal is
enabled
0 × 0106
P0.07
Setting of run
command set
mode
Run command
set mode
0: Keypad control
1: Terminal control 1 (STOP
key is inactive)
2: Terminal control 2 (STOP
key is enabled)
3: Serial communication 1
(STOP key is inactive)
4: Serial communication 2
(STOP key is enabled)
5: Terminal control 3 (STOP
and JOG keys are inactive)
0 ○ 0107
P0.08
Keypad direction
setting
Keypad direction
setting
0: Positive rotation 1: Reverse
rotation
0 ○ 0108
P0.09
Fundamental
frequency
Fundamental
frequency
3004GB and below:
0.10~650.0Hz
35R5GB and above:
0.10~400.0Hz
50.00Hz × 0109