DLM-600 installer & user manual Rev. 1.3 16-11-2011 6 / 39
- Protocol
Possible central station protocols for GSM are: Contact ID, SIA Level 2 and XSIA. The central station
protocol used for GPRS is SIA HS IP. Possible private GSM protocols are: Alarm siren, SMS text
message and speech (with optional speech board)
- Speech reporting
The DLM-600 can be expanded with an optional speech board for speech reporting to private
(mobile) telephone numbers.
- 3 LED’s for optical indication
3 LED’s for the status of the DLM-600 dialer. OP2 (green) indicates if the DLM-600 is operational.
OP4 (orange) will illuminate if there is a message in the buffer (GSM mode) and in GPRS mode it
indicates that the GPRS connection is operational. OP3 (red) will illuminate when the DLM-600
transmits a message.
- Programming
The DLM-600 is programmed with an Alphatronics programming cable (art. code 003834) and a
computer/laptop with AlphaTool software (art. code 004255) version 2.4 of higher. The AlphaTool
software can be used in combination with a modem to do remote programming.
- Dimensions
DLM-600 pcb only: 160 x 105mm
DLM-600 in synthetic cabinet (including power supply and battery pack): 250 x 190 x 70mm
- Operating temperature
0
o
C to 50
o
C
- Storage temperature
-20
o
C to +60
o
C (excluding battery pack)
- Humidity
85% relative humidity
Accessories
- Programming cable (art. code. 003834) and AlphaTool software (art. code. 004255).
De DLM-600 complies with the following European regulations:
EMC immunity EN50130-4 2003
Radio EN300220-3
Telephone TBR21 1998
Security class European norm EN60950
Alarm transmission EN50136-2-1 1998
ATS class 50136-1-1 D4, M4, T5, A3, S2, I3
The DLM-600 is manufactured according to the latest production methods and meets the RoHS
requirements. This implies that the components used and the soldering method (among others) is lead-
free.
The DLM-600 contains a periodic ‘Test Message’ which is an automatic test report, which is generated
by the DLM-600 itself. This option should be programmed as 24-hours (requirements state within 25
hours). If the DLM-600 is in idle state (no alarms) it will automatically transmit a test message every 24
hours.