EasyManua.ls Logo

Alstom MiCOM P546 - Page 50

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P54x/EN TD/La4 Technical Data
(TD) 2-20
MiCOM P543, P544, P545 & P546
TD
ISEF>3 Directional:
Non-Directional
Directional Fwd
Directional Rev
ISEF>3 Current Set: 0.005…0.8 In
SEF
ISEF>3 Time Delay: 0 s…200 s
ISEF>3 Intertrip: Enabled/Disabled
ISEF>4 as ISEF>3
ISEFN> Blocking
Bit 0 VTS Blks ISEF>1
Bit 1 VTS Blks ISEF>2
Bit 2 VTS Blks ISEF>3
Bit 3 VTS Blks ISEF>4
Bit 4 A/R Blks ISEF>3
Bit 5 A/R Blks ISEF>4
Bit 6 Not Used
Bit 7 Not Used
ISEF> Directional
ISEF> Char Angle: -95°…95° deg
ISEF> VNpol Set: 0.5…80 V
Wattmetric SEF
PN> Setting: 0...20 In
SEF
W
Neutral voltage displacement
(residual O/V NVD)
VN>1 Function:
Disabled
DT
IDMT
VN>1 Voltage Set: 1…80 V
VN>1 Time Delay: 0.00…100.00 s
VN>1 TMS: 0.5…100.0
VN>1 tReset: 0.00…100.00 s
VN>2 Status: Disabled/Enabled
VN>2 Voltage Set: 1…80 V
VN>2 Time Delay: 0.00…100.00 s
Thermal overload
Characteristic:
Disabled
Single
Dual
Thermal Trip: 0.08…4.00 In
Thermal Alarm: 50…100%
Time Constant 1: 1…200 mins
Time Constant 2: 1…200 mins
Power swing/out of step
(power swing)
Power Swing:
Blocking
Indication
PSB Reset Delay: 0.05…2.00 s
Zone 1 Ph PSB: Blocking/Allow Trip
(up to):
Zone 4 Ph PSB: Blocking/Allow Trip
Zone 1 Gnd PSB: Blocking/Allow Trip
(up to):
Zone 4 Gnd PSB: Blocking/Allow Trip
PSB Unblocking: Disabled/Enabled
PSB Unblock Delay: 0.1…10.0 s
PSB Reset Delay: 0.5…2.0 s
Out of step
OST (Out of Step Tripping) mode:
Disabled
Predictive and OST Trip
OST Trip
Predictive OST
Z5 Fwd Reach: 0.1…500.00/In
Z6 Fwd Reach: 0.1…500.00/In
Z5’ Rev Reach: 0.1…500.00/In
Z6’ Rev Reach: 0.1…500.00/In
R5 Res. Fwd: 0.1…200.00/In
R6 Res. Fwd: 0.1…200.00/In
R5’ Res. Rev: -0.1…-200.00/In
R6’ Res. Rev: -0.1…-200.00/In
α Blinder Angle: 20…90°
Delta t Time Setting: 0.02 s…1 s
Tost Time Delay Setting: 0 s…1 s
Undervoltage protection
V< Measur't Mode:
V<1 & V<2 Ph-Ph,
V<1 & V<2 Ph-N,
V<1Ph-Ph V<2Ph-N,
V<1Ph-N V<2Ph-Ph
V< Operate Mode:
V<1 & V<2 Any Ph
V<1 & V<2 3Phase
V<1AnyPh V<2 3Ph
V<1 3Ph V<2AnyPh
V<1 Function:
Disabled
DT
IDMT
V<1 Voltage Set: 10…120 V
V<1 Time Delay: 0.00…100.00 s
V<1 TMS: 0.5…100.0
V<1 Poledead Inh: Disabled/Enabled
V<2 Status: Disabled/Enabled
V<2 Voltage Set: 10…120 V
V<2 Time Delay: 0.00…100.00 s
V<2 Poledead Inh: Disabled/Enabled
Overvoltage protection
V> Measur't Mode:
V>1 & V>2 Ph-Ph,
V>1 & V>2 Ph-N,
V>1Ph-Ph V>2Ph-N,
V>1Ph-N V>2Ph-Ph
V> Operate Mode:
V>1 & V>2 Any Ph
V>1 & V>2 3Phase
V>1AnyPh V>2 3Ph
V>1 3Ph V>2AnyPh
V>1 Function:
Disabled
DT
IDMT
V>1 Voltage Set: 60…185 V
V>1 Time Delay: 0.00…100.00 s
V>1 TMS: 0.5…100.0
V>2 Status: Disabled/Enabled
V>2 Voltage Set: 60…185 V

Table of Contents