EasyManua.ls Logo

Alstom MiCOM P546 - Page 51

Alstom MiCOM P546
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data P54x/EN TD/La4
MiCOM P543, P544, P545 & P546
(TD) 2-21
TD
V>2 Time Delay: 0.00…100.00 s
V1>1 Cmp Funct:
Disabled
DT
IDMT
V1>1 Cmp Vlt Set: 60…110 V
V1>1 Cmp Tim Dly: 0.00…100.00 s
V1>1 CmpTMS: 0.5…100.0
V1>2 Cmp Status: Disabled/Enabled
V1>2 Vlt Set: 60…110 V
V1>2 CmpTim Dly: 0.00…100.00 s
Underfrequency protection
F<1 Status: Disabled/Enabled
F<1 Setting: 45.00…65.00 Hz
F<1 Time Delay: 0.00…100.00 s
F<2 Status
(up to):
F<4 Time Delay
All settings and options chosen from the
same ranges as per the 1st stage
F< Function Link:
Binary function link string, selecting which
frequency elements (stages 1 to 4) will be
blocked by the pole-dead logic
Overfrequency protection
F>1 Status: Disabled/Enabled
F>1 Setting: 45.00…65.00Hz
F>1 Time Delay: 0.00…100.00s
F>2 Status
(up to):
F>2 Time Delay
All settings and options chosen from the
same ranges as per the 1st stage
Rate-of-change of frequency
protection
(df/dt protection)
df/dt Avg. Cycles: 6…12
df/dt>1 Status: Disabled/Enabled
df/dt>1 Setting: 0.1…10.0 Hz
df/dt>1 Dir’n.: Negative/Positive/Both
df/dt>1 Time: 0.00…100.00 s
df/dt>2 Status:
(up to):
df/dt>4 Time
All settings and options chosen from the same
ranges as per the 1st stage.
Circuit breaker fail
CB Fail 1 Status: Disabled/Enabled
CB Fail 1 Timer: 0.00…10.00 s
CB Fail 2 Status: Disabled/Enabled
CB Fail 2 Timer: 0.00…10.00 s
Volt Prot Reset:
I< Only
CB Open & I<
Prot Reset & I<
Ext Prot Reset:
I< Only
CB Open & I<
Prot Reset & I<
WI Prot Reset: Disabled/Enabled
Undercurrent
I< Current Set: 0.02…3.20 In
ISEF< Current Set: 0.001…0.8 In
SEF
Poledead
V< : 10 …40 V
Supervision
VT Supervision
VTS Mode: Measured + MCB, Measured Only
or MCB Only
VTS Status: Disabled/Blocking/Indication
VTS Reset Mode: Manual/Auto
VTS Time Delay: 1 s...10 s
VTS I> Inhibit: 0.08....32 x In
VTS I2> Inhibit: 0.05...0.5 x In
Inrush Detection
I> 2nd Harmonic: 10%...100%
Weak Infeed Blk
WI Inhibit: Disabled/Enabled
I0/I2 Setting: 2...3
CTS Mode: Disabled, Standard, I Diff, Idiff +
Standard
CTS Status: Restrain, Indication,
CTS Reset Mode: Manual or Auto
CTS Time Delay: 0...10 s
CTS VN< Inhibit: 0.5 V...22 V
CTS i1>: 0.05*In...4.0*In
CTS i2/i1>: 0.05...1
CTS i2/i1>>: 0.05...1
Systems check
Bus-Line Synchronism and Voltage Checks
(System Checks)
P543 and P545 system checks:
Voltage Monitors
Live Voltage: 1.0…132.0 V
Dead Voltage: 1.0…132.0 V
Synchrocheck (Check Synch)
CS1 Status: Disabled/Enabled
CS1 Phase Angle: 0…90°
CS1 Slip Control:
None
Timer
Frequency
Both
CS1 Slip Freq: 0.02…1.00 Hz
CS1 Slip Timer: 0.0…99.0 s
CS2 Status
(up to):
CS2 Slip Timer
All settings and options chosen from the same
ranges as per the first stage CS1 element.
CS Undervoltage: 10.0…132.0 V
CS Overvoltage: 60.0…185.0 V
CS Diff Voltage: 1.0…132.0 V
CS Voltage Block:
None
Undervoltage

Table of Contents

Related product manuals