EasyManua.ls Logo

Alstom SHPM 101 - Page 248

Alstom SHPM 101
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE MANUAL R5888B
QUADRAMHO Chapter 5
Appendix A
Page 4 of 18
Test Test and method LED Comments
option indications
no.
43 Overvoltage level A–N A
detectors B–N B
(secondary inject C–N C
voltage
Pushbutton & push– Z2
button override
(operate push-
button or apply 0V
to SK1 Pin 9)
Low set current A Z3
level detectors
B AIDED TRIP
(secondary inject C SOTF
current)
Inhibit PSB opto input N V~FAIL
45 Self check of A–N A The LED lights
Zone 1 comparators B–N B for the appropriate
C–N C comparator if it
A–B Z2 passed the last
B–C Z3 self check. If all
C–A AIDED TRIP 8 LEDs are on
self check has
not occurred
46 Self check of A–N A As option 45
Zone 1 comparators B–N B
C–N C
A–B Z2
B–C Z3
C–A AIDED TRIP
47 Self check of A–N A As option 45
Zone 3 B–N B
comparators C–N C
A–B Z2
B–C Z3
C–A AIDED TRIP
Self check of Zone 6 A–B SOTF
comparator
Figure 3: Sheet 2