SERVICE MANUAL R5888B
QUADRAMHO Chapter 5
Appendix A
Page 12 of 18
Figure 7: Output test options
Test Output tested and switch to Output given on the rear terminals
option be set to the right and/or the monitor point box
60 “A” Indication SW8 Pressing the reset SK2–25
“B” Indication SW7 button causes the SK2–24
“C” Indication SW6 voltage on the monitor SK2–23
“Z2” Indication SW5 point box terminals SK2–22
“Z3” Indication SW4 (2 is 0V reference) to SK2–21
“AIDED TRIP” Indication SW3 fall from 24V to zero K2–20
Use high impedance SK2–19
"SOTF” Indication SW2 voltmeter SK2–18
“V~FAIL” Indication SW1
61 Fault locator A SW8 19A–1 C1–C2
Fault locator B SW7 19B–1 C3–C4
Fault locator C SW6 19C–1 C5–C6
Fault locator N SW5 19E–1 C7–C8
Power swing timer SW4 As for 60 SK2–7
62 Signal send SW8 85X–1, 85X–2, B1–B2, B3–B4 SK2–17
CRX annunciate SW6 SK2–9
Zone 2 trip alarm SW5 Z2–1 C9–19
Zone 3 trip alarm SW4 Z3–1 C11–C12
Aided trip alarm SW3 94Y–1 C13–C14
Switch on to fault SW2 98–1 C15–C16
Trip alarm
Fuse fail alarm SW1 97X–1 C17–C18
63 “POWER SWING” indication SW6
Any Z1, Z2, Z3 SW5
Block A/R SW4 96–1 B25–B26 SK2–6
Power swing alarm SW2 95–1 C19–C20 SK2–13
64 SOTF Enabled SW3 As for 60 SW2–5
88 ANY TRIP SW5 94–1, 94–2 B21–B22, B23–B24 SK2–11
TRIP 3Ph SW4 94T–1, 94T–2 B17–B18, B19–B20 SK2–12
TRIP A SW3 94A–1, 94A–2 B5–B6, B7–B8
TRIP B SW2 94B–1, 94B–2 B9–B10, B11–B12
TRIP C SW1 94C–1, 94C–2 B13–B14, B15–B16
Note: No contact will close until the appropriate SW switch is to the right and the reset button is
pressed.