Alstom SHPM 101 - Section 19. CURRENT TRANSFORMER REQUIREMENTS; 19.5 Selecting Zone 2 reach; 19.6 Selecting Zone 3 reach

Alstom SHPM 101
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE MANUAL R5888B
QUADRAMHO Chapter 1
Page 15 of 27
With K1 + K2 = 1.4 current level detector sensitivities:
=
4.8
x base settings = 3.43 x base settings
1.4
Required Zone 1 multiplier setting =
required Zone 1 reach
Z
Ph
=
0.292 x I
n
=
0.292 x 5
= 1.043
(K1 + K2) 1.4
Zone 1 multiplier = (K11 + K12 + K13) K14
Select K11 = 1
K12 = 0.0
K13 = 0.04
K14 = 1
Actual Zone 1 setting = (K11 + K12 + K13) K14 x Z
Ph
= 1.04 x 1 x
1.4
= 0.291
/70° ohms
5
19.5 Selecting Zone 2 reach
Required Zone 2 reach = +50% (JUNE – JULY line impedance) MAY – JUNE
line impedance.
Required Zone 2 reach = (10 + 0.5 x 20) (0.171 + j0.47) ohms
= 10.0/70° ohms primary
= 0.73/70° ohms secondary
Required Zone 2 multiplier setting =
required Zone 2 reach
Z
Ph
=
0.73 x 5
= 2.61
1.4
Zone 2 multiplier = (K21 + K22) K24
Select K21 = 2
K22 = 0.6
Actual Zone 2 setting = (K21 + K22) K24 x Z
Ph
= 2.6 x 1 x
1.4
= 0.728
/70° ohms
5
19.6 Selecting Zone 3 reach
Required Zone 3 forward reach = +125% (JUNE – JULY line impedance) MAY –
JUNE line impedance.
Required Zone 3 forward reach = (10 + 1.25 x 20) (0.171 + j0.47)
= 17.5
/70° ohms primary
= 1.28 /70° ohms secondary
Required Zone 3 forward reach multiplier
=
required Zone 3 forward reach
|Z
Ph
|