EasyManua.ls Logo

Alstom SHPM 101 - Page 303

Alstom SHPM 101
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SERVICE MANUAL R5888B
QUADRAMHO Chapter 6
Addendum A
Page 3 of 15
Test option no. Test and method LED indications Comments
47 Self check of Zone 3 A–N A As option 45
comparators B–N B
C–N C
A–B A–B Z2
B–C Z3
C–A AIDED TRIP
Self check of Zone 6 A–B SOTF
comparator
V~FAIL
50 Zone 1 comparators A–N A As option 40.
(Secondary inject B–N B
Zone 1 fault) C–N C
A–B Z2
B–C Z3
C–A AIDED TRIP
Breaker open opto input SOTF
(apply rated volts to A3–A4)
Reset Zone 1 extension opto input V~ FAIL
(apply rated volts to A1 – A2)
The “Zone 1 extension” opto
is redesignated “miniature circuit
breaker open” opto when this
version has been supplied.
51 Zone 2 comparators A–N A As option 41.
(Secondary inject B–N B
Zone 2 fault) C–N C
A–B Z2
B–C Z3
C–A AIDED TRIP
Signal receive opto input SOTF
(apply rated volts to A9 – A10)
Channel in service opto input V~ FAIL
(apply rated volts to A7 – A8).
The “signal receive” opto also can
be used to “reset Zone 1 extension”
for the appropriate thumbwheel
selection option.
Figure 1: Sheet 3

Table of Contents

Related product manuals