SERVICE MANUAL R5888C
QUADRAMHO Chapter 2
Page 30 of 74
Test Output tested and switch to be Output given on the rear terminals
option set to the right and/or the monitor point box
no.
60 “A” indication SW8 Pressing the reset button SK2–25
“B” indication SW7 causes the voltage on the SK2–24
“C” indication SW6 monitor point box terminals SK2–23
“Z2” indication SW5 (2 is 0V reference) to fall SK2–22
“Z3” indication SW4 from 24V to zero. Use a SK2–21
“AIDED TRIP” indication SW3 high impedance SK2–20
“SOTF” indication SW2 voltmeter SK2–19
“V– FAIL” indication SW1 SK2–18
61 Fault Iocator A SW8 19A–1 C1–C2
B SW7 19B–1 C3–C4
C SW6 19C–1 C5–C6
N SW5 19E–1 C7–C8
Power swing timer SW4 As for 60 SK2–7
Hysteresis SW1 Internal
62 Signal send SW8 85X–1,85X–2,B1–B2,B3–B4 SK2–17
CRX annunciate SW6 SK2–9
Zone 2 trip alarm SW5 Z2–1 C9–10
Zone 3 trip alarm SW4 Z3–1 C11–C12
Aided trip alarm SW3 94Y–1 C13–C14
SOTF trip alarm SW2 98–1 C15–C16
Fuse fail alarm SW1 97X–1 C17–C18
63 MRI SW8 Internal
Self Check SW7 Internal
“POWER SWING” indication SW6
Any Z,Z2,Z3 SW5 Any Z1,Z2,Z3 SK2–6
Block A/R SW4 96–1 B25–B26
SK2–13
Extend Zone 1 SW3 Internal
Power swing alarm SW2 95–1 C19–C20
64 Pole dead C SW6 Internal
Pole dead B SW5 Internal
Pole dead A SW4 Internal
SOTF Enable SW3 SK2–5
DICO SW2 Internal
ENF SW1 Internal
88 Any trip SW5 94–1,94–2, B21–B22,B23–B24,
SK2–11
Trip 3 phase SW4 94T–1,94T–2, B17–B18,B19–B20,
SK212
Trip A SW3 94A–1, 94A–2, B5–B6, B7–B8
Trip B SW2 94B–1,94B–2, B9–B10, B11–B12
Trip C SW1 94C–1,94C–2, B13–B14,B15–B16
Table 7: Output test options