EXIT return from the local Menu to the normal operation of the transmitter
UNIT menu process variable units. Options:
IN_H2O inches of water at a temperature of 68 ° Fahrenheit
IN_HG inches of mercury at a temperature of 68 ° Fahrenheit
FT_H2O foot of water a temperature of 68 ° Fahrenheit
MM_H2O mm of water at a temperature of 68 ° Fahrenheit
MM_HG mm of mercury at 0 ° C
PSI
BAR bar
MBAR millibar
G/SQCM grams per square centimetres
KG/SQCM kilogram per square centimetres, technical atmosphere
PA pascal
KPA kilopascal
TORR tor (mm Hg)
ATM physical atmosphere
M_H2O meter of water at 4 ° C
MPA megapascal
INH2O@4 inch of water at a temperature of 4 ° C
MMH2O@4 mm of water at 4 ° C
DAMPIN menu damping of process variable [s]. You can choose 0,2,5,10,30,60 [s]
TRANSF type of current output characteristic Menu. Options:
LINEAR linear
SQRT square root
SPECIA user’s special
SQUARE square
%SQRT menu of, point insensitivity of square root characteristics. To select 0%, 0.2%, 0.4%, 0.6%,
0.8%, 1.0% range
PVZERO pressure zeroing
.
SETURV setting the upper range value by the done pressure
SETLRV setting the lower range of values set by the done pressure
RESET reboot your transmitter
LCD1VR assigning a process variable to LCD1. Options:
CURREN current in the line in [mA]
PERCEN percent of the set range - controling in%
LCD2VR assigning a process variable to LCD2. Options:
PRESS pressure value in units UNIT
USER pressure value in user’s units
Scaling of the user range and record of the user units can be made using a computer or
communicator, see HART command No. 244.245
SENS_T sensor temperature value in the pressure header in °
CPU_T CPU electronics board temperature value - in º C