TABLE 1: DIAGNOSTIC CODES
Diagnostic
Code Failure Mode Action Reset
E1
Internal Humidity or
Temperature Sensor
Open or Shorted
1. Cycle power to clear error code� Unplug the unit from the outlet or switch
the ON/OFF Power Switch (if equipped) to the OFF position for at least 10
seconds before restoring power�
2. If error code reoccurs, replace User Interface, Part #5445.
Cycle Power
E2
High Refrigeration
Pressure
1. Verify that the fan works, the backow damper swings freely, and there is
no blocked or restricted ductwork�
2. If the fault persists, call Technical Support�
Cycle Power
E3
Model 76
Remote Control
Communication Loss
1. Check connections between Model 76 and dehumidier user interface.
Terminals should be fully inserted and secured in the user interface and
Model 76 control terminals�
2. If connections are correct and secure, turn off the dehumidier and
remove the Model 76� Use a short section of 4-wire cable to reconnect the
Model 76 to the user interface. Turn the dehumidier back on and increase
the dryness level setting on the Model 76. If the dehumidier turns on, a
problem exists with the wiring between the dehumidier and control.
3. If the dehumidier does not turn on, call Technical Support.
Self-Correcting
E4 Insufcient Capacity
1. Check the frost sensor connection at the power board� The terminal
should be fully seated on the power board pins�
2. Remove the side access panel and verify that the sensor is secured to the
suction line�
3. If the sensor is connected and secured to the refrigeration line, proceed to
the next step.
4. Reset the fault by cycling power to the dehumidier.
5. Turn the humidity setting down (below room/home humidity level) to
make a dehumidication call.
6. Allow the fan and compressor to run for approximately 10-15 minutes and
then enter diagnostic test mode by simultaneously pressing the button
and MODE button for 3 seconds. The LCD will display:
• the temperature measured by the internal sensor while also displaying
the words AIR SAMPLING and ON
• the humidity measured by the internal sensor while also displaying %RH
and the word ON
• the frost sensor temperature while also displaying the word ON�
Scroll through these values and by using the or button�
7. Record values and call Technical Support.
Cycle Power
E5
High Temperature
Thermistor Failure
1. Check the high temperature sensor connection at the power board� The
terminal should be fully seated on the power board pins�
2. Remove the side access panel and verify the sensor is not damaged and
connected to the refrigeration line coming from the compressor�
3. If the sensor is connected and secured to the refrigeration line, it may
need to be replaced with Part #5456 – contact Technical Support to
conrm.
Cycle Power
TROUBLESHOOTING
Technical support is available Monday through Friday 7:00 a�m�
to 5:00 p�m� CST at 800�334�6011� Use the guides on the following
pages to identify and correct system faults� Contact Technical
Support before replacing the unit or any components and for
additional troubleshooting�
DIAGNOSTIC CODES
When an error occurs, the Diagnostic Code along with SERVICE
REQUIRED will be displayed on the user interface screen�
12 English