INSTALLING THE DRAIN
USING HARD PIPE:
• Install a 3/4” PVC slip x 3/4” MNPT PVC tting to the
dehumidier and use 3/4” nominal PVC Schedule 40 pipe to
run the condensate line to the nearest oor drain or to an
outside location that slopes away from the building�
• Always maintain a constant downward slope in drain
piping. Ensure that drain tubing does not interfere with
removal of the side panel or lter door.
• Do not use metal ttings and only hand-tighten threaded
ttings. PTFE thread seal tape is recommended for threaded
connections�
• Install a tee or three-way elbow at the dehumidier outlet
with a small, capped vertical tube (do not cement cap in
place) to allow for cleaner to be poured into the drain line
(see FIGURE 6).
• PVC primer and cement is recommended for slip-t
connections (do not cement threaded connections).
USING FLEXIBLE TUBING:
• Install the provided 3/4” NPT x 3/4” hose barb tting and use
3/4” I.D. exible drain tubing. Hand-tighten the tting to the
dehumidier. PTFE thread seal tape is recommended for
threaded connections�
• Always maintain a constant downward slope from the
dehumidier to the nearest oor drain or condensate pump,
and do not allow soft tubing to curl up, which may result in
air lock.
INSTALLING THE CONDENSATE PUMP
• The AprilAire Model 4856 condensate pump is capable of
lifting water up to 22 feet�
• The dehumidier can be elevated (while remaining level) to
increase downward slope for proper draining�
• Wire the oat switch terminals to the normally closed
contacts on the condensate pump (see FIGURE 14).
INSTALLING DUCTWORK
Add ductwork to the inlet and outlet of the dehumidier to
ensure dehumidied air is circulated throughout the crawl
space and reduce the noise level of the dehumidier. Point
the inlet and outlet ducts in opposite directions to minimize
recirculation of dehumidied air.
• Maximum recommended total duct length is 100 feet.
• To avoid pulling in dirt and other particles, do not lay intake
duct on the oor of the crawl space.
NOTE: Maximum allowable static pressure for this unit is 0.4" w.c.
A
B
C
D
E
FIGURE 11: DRAIN AND CONDENSATE PUMP INSTALLATION
A. FLOAT SWITCH WIRE
B.
3
⁄4" MNPT x
3
⁄4" BARB
FITTING
(INCLUDED)
C.
3
⁄4" CLEAR PVC
TUBING (INCLUDED)
D. CONDENSATE PUMP
(PART #4856)
E. 8" DIAMETER
INSULATED
FLEX DUCT
90 -2306
8 English