10.3 CONNECTING TO POWER SUPPLY
10.4 ELECTRICAL TESTING
22
The heat pump is supplied with a 3 point earthed plug and
may be run off a power socket where such connection is
complient with National wiring regulations AS.3000 and/or
such requirements as stipulated by local authorising bodies.
Should permanente connection to power supply be required
by National wiring regulations AS.3000 and/or local
authorising bodies. A qualified electrician should remove
the units plug and utilise the power supply cord to wire the
system into a junction box with isolation switch.
To ensure the heat pump will not overload the power supply and to provide optimum saftey
running conditions, electrical connection to this product is recommended as an isolated
circuit rated at 16A RCD/MCB or RCBO with a test button function.
Electrical recomendations
When conducting an insulation test using a Megger on this appliance, observe the
following:
permitted where the appliance is approved to a Standard applicable to that class of
appliance.
This appliance is categorised and certified as a ‘stationary Class 1 motor operated
appliance’ and therefore satisfies the requirements of AS/NZS 60335.2.40 for leakage
current and electric strength. As such, this appliance complies with the insulation
resistance requirements of AS/NZS 3000.
This appliance contains electronic components, when performing insulation tests
(500 Volts) this MUST ONLY be conducted the across active terminal to earth and then
across the neutral terminal to earth. Tests between the active to neutral terminals MUST
NOT be performed as this WILL damage the electronic components.