Air-to-water Heat Pump
55
Note: firstly please cut off the power supply and discharge refrigerant out of the unit.
Operation Procedure
Illustration
AG4HP061PH
Remove the fixing bolts and electric box.
Remove fixing bolts, desolder connection points between
gas/liquid lines of the plate-type heat exchanger and the
main unit, and then remove the water system.
Note:when desoldering the connection joint, pay attention to
covering the solder joints with a wet cloth to avoid high
temperature damage.
Desolder connection points of the 4-way valve, and remove
the pipelines of the 4-way valve.
Note:when desoldering the connection joint, pay attention to
covering the solder joints with a wet cloth to avoid high
temperature damage.
Desolder connection points of the suction lines and remove
suction lines.
Note:when desoldering the connection joint, pay attention to
covering the solder joints with a wet cloth to avoid high
temperature damage.