Chapter 3: Configuration and commissioning
94 2X Series Installation Manual
• Activation with no delay for zones 140 to 163
• No activation for remote zones (in this example, zones 1 to 99 and zones 164
to 9999 are remote zones). Remote zones are indicated as REMT on the
LCD.
This programmed output activation can be configured with the Configuration
Utility (recommended) or via the Activation configuration menu at the control
panel.
General delays
Select the General delays option to configure region-specific investigation times
or advanced delay options.
Configurable options for general delays are shown in the table below.
Table 54: Configurable options for general delays
Investigation mode. Enables regional investigation time modes
(maximum acknowledgement time, extended fire routing delay).
Investigation time. Configures regional investigation time delays
(maximum acknowledgement time, extended fire routing delay).
Warning time. Configures the warning time when the control
panel is configured to use a warning tone for a second stage
sounders application. For standard applications with no warning
tone requirement, this time must be 0.
Warning time (extended). If checked, the warning tone (where
configured) will change to the evacuation tone only if a manual
call point alarm is detected.
Sounder silence disable time. Disables silencing sounders with
the Sounder Start/Stop button for a preconfigured time when a
sounder delay is running.
To configure general delays:
1. Select Field setup from the Main menu, and then select Activation
configuration.
2. Select General delays.
3. Select Investigation mode, and then select the type of investigation mode
required.
See “Investigation mode” on page 95 for more information on this option.
4. If an investigation mode is selected, select Time, and then enter the time
value (in seconds).
See “Investigation time” on page 96 for more information on this option.
5. If warning tones are required (for second stage sounders), select Warning
time, and then enter the time value (in seconds).