Chapter 3: Configuration and commissioning
2X Series Installation Manual 45
The Disable/Enable menu
Use the Disable/Enable menu to disable and enable the system features and
devices. Features and devices can be disabled remotely if the control panel is
part of a fire network. Disabled features and devices do not indicate faults or fire
alarms.
Note: Changes to disable/enable configuration at this user level are not stored in
the control panel configuration and are not included in any saved configuration
files.
The following features or devices can be disabled or enabled from this menu:
Zones
Devices
Control panel inputs and outputs
Output groups (sounder, fire routing, fire protection, or program)
Disabling a system feature or device
To disable a feature or device:
1. Select Disable/Enable from the Main menu.
2. Select Disable (or Remote Disable if the feature or device is not local to the
control panel).
3. Select the corresponding option (zones, devices, etc.).
4. For local disablements, select the feature or device to be disabled, and then
press the jog dial to confirm the disablement.
For remote disablements, enter the Firenet ID of the feature or device to be
disabled, and then press the jog dial to confirm the disablement.
5. Press F2 (Exit) to exit the menu.
Repeat to enable a disabled feature or device.
Notes
Active outputs cannot be disabled.
Devices or zones in alarm are not disabled until the control panel is manually
reset.
In maintenance level operation, to disable Class A outputs each output used
must be disabled (for example, if OUT1 and OUT2 are combined to create a
single Class A output, then both OUT1 and OUT2 must be disabled
individually).

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing