Chapter 3: Configuration and commissioning
2X Series Installation Manual 55
Regional options
Select Regional options to set the regional operating mode. Available options are
shown in the table below.
Table 21: Regional operating modes
-2 (default) European Union
-2 Evacuation European Union (Spain)
21-100 [1] European Union (Belgium)
2535/2575 [2] European Union (Holland)
dS 2540 [1] European Union (Germany)
1] See the corresponding marketplace manuals for additional installation and operation
for these regional operating modes.
[2] Implements NEN 2535 for fire and repeater panels and NEN 2575 for evacuation panels.
To change the control panel operation mode:
1. Select Panel setup from the Main menu.
2. Select Regional options.
3. Select the operating mode.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit)
Remember to apply saved settings from the Main menu.
Firenet configuration
Select the Firenet options to configure the control panel fire network and repeater
settings shown in the table below.
Table 22: Firenet configuration options
Displays all detected control panels, to add control panels to the
fire network, or to remove control panels from the network. By
default new control panels detected do not communicate with the
network.
opmode Configures the control panel network operation mode (stand-alone
panel, networked panel, or networked repeater panel).
Configures the control panels in the network that the control panel
being configured will repeat.
controls Configures global control options for networked control panels and
repeaters.
Configures the types of events to repeat from other control panels
in the fire network.