Chapter 4: Maintenance
106 2X Series Installation Manual
Fire alarm system maintenance
To ensure correct functioning of your control panel and fire alarm system, and
compliance with all European regulations, the following maintenance checks
should be followed.
Caution: Ensure that fire routing (where configured) has been disabled or that
the fire brigade has been notified of any planned fire alarm tests.
Quarterly maintenance
Contact your installation or maintenance contractor to carry out a quarterly
inspection of the fire alarm system.
This must test at least one device per zone and verify that the control panel
responds to all fault and alarm events.
The control panel power supply should be checked and the batteries tested using
the Battery test” menu option (see Battery test fault indicationson page 107).
Annual maintenance
Contact your installation or maintenance contractor to carry out an annual
inspection of the fire alarm system.
This must test all system devices and verify that the control panel responds to all
fault and alarm events. All electrical connections must be visually inspected to
make sure that they are securely fastened, that they have not been damaged,
and that they are appropriately protected.
Cleaning
Keep the outside and inside of the control panel clean. Carry out periodic
cleaning using a damp cloth for the outside. Do not use products containing
solvents to clean the unit. Do not clean the inside of the cabinet with liquid
products.

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing