EasyManuals Logo

Aritech 2X Series User Manual

Aritech 2X Series
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #78 background imageLoading...
Page #78 background image
Chapter 3: Configuration and commissioning
72 2X Series Installation Manual
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select DACT config.
3. Select CMS config, and then Select the CMS to configure (1 to 6).
4. Configure all required settings.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
PSTN configuration
Select the PSTN configuration option to configure public switched telephone
network settings. Configuration options are shown in the table below.
Table 33: PSTN configuration options
Option
Description Default value
Ccode
Configures the PSTN country code [1] 099
Line 1
Enables or disables line 1 [2] Disabled
Line 2
Enables or disables line 2 [2] Disabled
Retries
Configures the maximum number of times the
number is dialled
05
Kissoff
Configures the kiss-off acknowledgement time 48 x 10 ms
] See Appendix B ā€œPSTN country codesā€ on page 119 for a complete list of country codes.
To change the configuration:
1. Select Panel setup from the Main menu.
2. Select Other settings, and then select DACT config.
3. Select PSTN config.
4. Configure all required settings.
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.

Table of Contents

Other manuals for Aritech 2X Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X Series and is the answer not in the manual?

Aritech 2X Series Specifications

General IconGeneral
CertificationsEN54-2, EN54-4
Power Supply230V AC, 50Hz
Battery Capacity7Ah
Current ConsumptionStandby: 50mA
Humidity RangeUp to 95% RH, non-condensing