4 - Operation
4.3.2 SETPOINT CONFIGURATION
Setpoint
type
see table 3
Stored
Setpoint Tracking
see page 43
no/ yes
Setpoint slope
time units
P.Sec/
P.Min/
P.Hr
Remote Setpoint
input
see table 4
not displayed if the
frequency input is present
Remote Setpoint
Slope enable [1]
no / yes
Tab. 4 Rem. Setpoint
Value Description
0=5
0…5 Volt
1=5
1…5 Volt
0=20
0…20 mA
Tab. 3
4=20
4…20 mA
Setpoint type
0=10
reM.t
Remote - trim
0…10 Volt
érs.In
loc.t
Local - trim
l=r
Local/remote only
reM
Remote only
loc
Local only
Value Description
éS.P.ty
Prog
Programmed (option)
[1] Not available with Setpoint
Programmer option