70
8 - Technical Specifications
Features
at 25°C env. temp.
Description
Remote
Setpoint
Not isolated
accuracy 0.1%
Current: 0/4...20mA: Rj = 30Ω
Bias in engineering units and ± range
Ratio: -9.99… +99.99
Local + Remote Setpoint
Voltage: 1... 5, 0... 5, 0... 10V: Rj = 300kΩ
Potentiometer 100Ω... 10kΩ
Digital inputs
3 logic
The closure of the
external contact
produces any of the
following actions:
Auto/Man mode change, Local/Remote Setpoint mode change, 3 Stored Setpoint activation, keyboard lock, measure
hold, slope inhibit and output forcing
Program Hold/Run (if option installed), Program Selection and Skip to Next Segment
Operating mode
and Outputs
1 single,
split range or
double action
PID loop or
ON/OFF with
1, 2,3 or 4
alarms
Single
action
Split range
Control output Alarm Alarm Alarm Alarm Retransmission
Main Secondary AL1 AL2 AL3 AL4 PV / SP
OP1
Relay/Triac
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
OP5
Analog./Digital
OP6
Analog./Digital
OP5
Analog./Digital
OP1
Relay/Triac
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
OP6
Analog./Digital
OP5
Analog./Digital
OP6
Analog./Digital
OP1
Relay/Triac
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
Double
action
Heat/Cool
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
OP5
Analog./Digital
OP6
Analog./Digital
OP1
Relay/Triac
OP5
Analog./Digital
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
OP6
Analog./Digital
OP5
Analog./Digital
OP2
Relay/Triac
OP1
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
OP6
Analog./Digital
OP5
Analog./Digital
OP6
Analog./Digital
OP1
Relay/Triac
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
Valve drive
OP1
Relay/Triac
OP2
Relay/Triac
OP3
Relay/Triac
OP4
Relay/Triac
OP5
Analog./Digital
OP6
Analog./Digital
Feedback valve position
OP1
Relay/Triac
Auxiliary inputs
x5-uk-ed5 17-09-2009 14:53 Pagina 70