Operation
Parameter listing
Menu
Submenu
Parameter
Name Description Range
Factory
settings
0 NETWORK
0. 2 BUS Network
0. 2. 0 Network Presence Indication of devices connected via BUS Boiler
Remote Modem
OpenTherm Gateway
1
0. 4 User interface
0. 4. 0 Zone to be set by display 1 - 3 1
0. 4. 1 Backlight timing 1 min - 24 hours 10
min
0. 4. 3 Time Program service type Select the time program service type
according to Ebus devices present in your
network
0 = Time programs
1 = Extended time
programs
0
0. 4. 4 Reset System Interfce OK = Yes, BACK = No
4 Zone1 Parameters
4. 0 Setpoint
4. 0. 0 T Day Room temperature set point for day period 10 - 30 (°C)
20
4. 0. 1 T Night Room temperature set point for night
period
10 - 30 (°C) 15
4. 0. 2 T set Z1 Temperature setpoint zone 1
( Limited by Para 4.2.5 and Para 4.2.6 )
40°C - 82°C
20°C - 45°C
75
20
4. 0. 3 Zone frost temperature 2 - 15 (°C) 5
4. 1 Summer/Winter Changeover
4. 1. 0 S/W function activation 0 = OFF, 1 = ON (only active when outside
WHPSHUDWXUHLQÀXHQFH
0 - 1
0
4. 1. 1 S/W temperature threshold 0 - 30 (°C) 15
4. 1. 2 S/W delay time Time before S/W changeover becomes
active
0 - 300 (min) 30
4. 2 Zone1 Settings
4. 2. 0 Zone temperature range 0 = Low Temp (LT)
1 = High Temp (HT)
0 - 1
1
4. 2. 1 Thermoregulation 0 = Fix Flow T
1 = Basi Thermoreg
2 = Room T Only
3 = Outdoor T Only
4 = Room+Outdoor T
0 - 4 0