EasyManuals Logo

Atag XL75W User Manual

Atag XL75W
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
86
Commissioning
Flue gas analysis
Low load (Step 2/3)
Step 2: O
2
/ CO
2
check on low load
Setting the low load
The low load of each engine or of
the complete boiler can be set by
you as follows:
- Press the “–” button until you
reach 0%;
- Press OK;
The boiler will switch to minimum
power output (low load) of the
boiler; the screen shows 0%
(heating capacity).
The O
2
value at low load must lie
higher than the O
2
value at full load.
The measuring procedure must be
carried out, until a stable measuring
result is achieved. Please contact
ATAG, if the values should lie outside
of the applicable tolerances.
End of measuring:
- Press the back button for 5 seconds
to exit chimney sweep mode.
This completes the procedure.
The maximum duration of the
commissioning function, without
interruption, is 20 minutes.
O
2
/ CO
2
check on low load (Step 2)
Low load Natural gas (G20) Propane (G31)*
O
2
Minimal 0,5% higher than measured on full load Minimal 0,2% higher than measured on full load
Maximum 6,3% Maximum 6,5%
CO
2
Minimal 0,3% lower than measured on full load Minimal 0,1% lower than measured on full load
Minimum 8,2% Minimum 9,5%
Values are valid with closed cover/air box. *only possible if LPG conversion kit is installed

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Atag XL75W and is the answer not in the manual?

Atag XL75W Specifications

General IconGeneral
BrandAtag
ModelXL75W
CategoryBoiler
LanguageEnglish

Related product manuals