68
Operation
Parameter listing
Menu
Submenu
Parameter
Name Description Range
Factory
settings
25. 0. 7 &+GLႇHUHQWLDOWHPSHUDWXUH 0 - 20°C 0
25. 0. 8
CH/DHW shifting priority time 0 - 65535min. 0
25. 1 System Settings
25. 1. 0
Thermoregulation
0 = OFF
1 = ON
0 - 1
1
25. 1. 1
External temperature correction -3 - 3°C 0
25. 1. 2 Boost Time 0 -60min. 0
25. 1. 3 Plant frost protection
0 = OFF
1 = ON
0 - 1
0
25. 1. 4
T Gradient 0 -15°C 5
25. 1. 5
System Pump Overrun 0 - 255min. 5
25. 1. 6
System pump activation logic
0 = Always active
1 = Heating only
0 - 1 0
25. 1. 7
System tank solar integration
0 = Absent
1 = Present
0 - 1
0
25. 2 Domestic Hot Water
25. 2. 0 DHW Setpoint Temperature 40 - 65°C 65
25. 2. 1
Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 - 2 0
25. 2. 2 System DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2
0
25. 2. 3 Anti-legionella Function
0 = OFF
1 = ON
0 - 1
0
25. 2. 4 System DHW charge mode
0 = Charge
1 = Full charge
2 = Full charge Legio
0 - 2
0
25. 2. 5
System DHW Circulating Pump Release
0 = Release
1 = Time Program
2 = Special Time Program
0 - 2
0
25. 2. 6
System DHW Charging Priority
0 = Absolute
1 = Shifting
2 = None
0 - 2
0