Atag XL75W - Page 70

Atag XL75W
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70
Operation
Parameter listing
Menu
Submenu
Parameter
Name Description Range
Factory
settings
26..32. 4 System Setting
26..32. 4. 0 Thermoregulation
0 = OFF 1 = ON
0 - 1 0
26..32. 4. 1 External temperature correction T7 -3 tot 3 °C 0
26..32. 4. 2 Boost time 0 - 60 min 0
26..32.
4. 3 Plant frost protection
0 = OFF 1 = ON
0 - 1 0
26..32. 4. 4 T Gradient 0 - 15 °C 5
26..32.
4. 5 System Pump Overrun 0 - 255 min 5
26..32.
4. 6 System tank solar integration
0 = Absent 1 = Present
0 - 1 0
26..32.
4. 7 CH/DHW shifting priority time 0
26..32. 5 Domestic Hot Water
26..32. 5. 0
DHW Setpoint Temperature 40 - 65°C 65
26..32. 5. 1
Comfort Function
0 = Disabled
1 = Time Based
2 = Always Active
0 - 2 0
26..32. 5. 2
System DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2
0
26..32. 5. 3 Boiler DHW Mode
0 = CH Only
1 = DHW Tank NTC
2 = DHW Tank Thermostat
0 - 2 0
26..32. 5. 4
Anti-legionella Function
0 = OFF
1 = ON
0 - 1 0
26..32. 5. 5
Boiler DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2
0
26..32. 5. 6
System DHW Charging Type
0 = Recharging
1 = Full charging
2 = Full charging Legio
0 - 2
0
26..32. 5. 7
Boiler DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2 0
26..32. 5. 8
System DHW Circulating Pump Release
0 = Release
1 = Time Programs
2 = Circ Pump special Time Programs
0 - 2 0