UL/cUL versions
For UL designed industrial control panels, calculations for cable sections and fuses are done according to
UL508a (Industrial control panels).
For cUL, calculations for cable sections and fuses are done according to CSA22.2 (Canadian electrical code).
Standard conditions: maximum 3 copper conductors in raceway or cable with 85-90˚C (185-194 ˚F)
insulation at ambient temperature 30 ˚C (86 ˚F), operating at nominal voltage; cables not grouped with other
cables.
Worst case conditions: ambient temperature > 30 ˚C (86 ˚F), max. 3 copper conductors in raceway or cable
with 85-90 ˚C (185-194 ˚F) insulation at 46 ˚C (115 ˚F) ambient temperature and operating at nominal voltage.
Cables not grouped with other cables.
Fuse size is the maximum fuse size in order to protect the motor against short circuit. For cUL fuse HRC form
II, for UL fuse class RK5.
If the local conditions are more severe then the described standard conditions, the cables and fuses for worst
case conditions should be used.
Recommended cable size
Type V Hz Approval I
tot
P
(1)
I
tot
FF
(1)
Recommended wire
section (2)
Recommended wire
section (3)
Main
fuses
(A) (4)
GA 15 230 50 IEC 62 67
4 x 25 mm
2
4 x 35 mm
2
80
GA 15 400 50 IEC 36 41
4 x 10 mm
2
4 x 16 mm
2
50
GA 15 500 50 IEC 29 34
4 x 10 mm
2
4 x 16 mm
2
50
GA 15 380 60 IEC 36 41
4 x 10 mm
2
4 x 16mm
2
50
GA 15 200 60 UL/cUL 67 72 4 x AWG2 4 x AWG2 100
GA 15 230 60 UL/cUL 58 64 4 x AWG3 4 x AWG2 80
GA 15 460 60 UL/cUL 29 34 4 x AWG6 4 x AWG6 50
GA 15 575 60 UL/cUL 23 29 4 x AWG8 4 x AWG6 40
GA 18 230 50 IEC 74 79
4 x 35 mm
2
4 x 50 mm
2
100
GA 18 400 50 IEC 43 48
4 x 16 mm
2
4 x 25 mm
2
63
GA 18 500 50 IEC 34 39
4 x 10 mm
2
4 x 16 mm
2
50
GA 18 380 60 IEC 44 49
4 x 16 mm
2
4 x 25 mm
2
63
GA 18 200 60 UL/cUL 84 89 4 x AWG2 4 x AWG1 125
GA 18 230 60 UL/cUL 72 77 4 x AWG3 4 x AWG2 100
GA 18 460 60 UL/cUL 36 41 4 x AWG6 4 x AWG4 50
GA 18 575 60 UL/cUL 29 34 4 x AWG6 4 x AWG6 50
GA 22 230 50 IEC 91 97
4 x 50 mm
2
4 x 70 mm
2
125
GA 22 400 50 IEC 54 59
4 x 25 mm
2
4 x 35 mm
2
80
GA 22 500 50 IEC 43 48
4 x 16 mm
2
4 x 25 mm
2
63
GA 22 380 60 IEC 56 61
4 x 25 mm
2
4 x 35 mm
2
80
GA 22 200 60 UL/cUL 103 108 4 x AWG1/0 4 x AWG1/0 125
GA 22 230 60 UL/cUL 94 99 4 x AWG1 4 x AWG1/0 125
GA 22 460 60 UL/cUL 47 52 4 x AWG4 4 x AWG3 80
Instruction book
2920 7083 31 147