The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, one of the following fault
signals is displayed: TSO FAULTS or TSC FAULTS (menu S1).
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SEATING MODE (M11)
VIEW (M110)
EDIT (M111)
OPEN POSITION (M11_0)
CLOSED POSITION (M11_1)
Default value: LIMIT
Step by step:
1. Set selector switch to position 0 (OFF).
2.
Press C and hold it down for approx. 3 seconds.
➥
Display indicates:
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3.
Press .
➥
Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4.
Press .
➥
Display indicates:
SETTINGS M11
SEATING MODE
TORQUE
LOCAL CONTROLS
5.
Press .
➥
Display indicates:
SEATING MODE M110
VIEW
EDIT
Use and to select between VIEW and EDIT.
39
SA 07.1 – SA 16.1/SAR 07.1 – SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTU Commissioning (basic settings)