12. Enter password:
Press 4 x = 0000 (default factory password).
EDIT M1110
OPEN POSITION
CLOSED POSITION
EDIT M1111
OPEN POSITION
CLOSED POSITION
Use and to select between OPEN POSITION and CLOSED POSITION.
13.
Press .
Display shows the set value:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT C:ESC
Use and to select between OPEN POSITION and CLOSED POSITION.
14.
Press again to enter the edit mode.
Display indicates:
EDIT M1110
OPEN POSITION
LIMIT
:EDIT :OK C:ESC
EDIT M1111
CLOSED POSITION
LIMIT
:EDIT :OK C:ESC
15. Set new value:
Press .
41
SA 07.1 SA 16.1/SAR 07.1 SAR 16.1 Control unit: electromechanic
AC 01.1 Intrusive Modbus RTU Commissioning (basic settings)